L SERIES

KL-WL-PL SERIES GENERAL FEATURES
Humidity:
Measuring Range : 0…100%rh
Accuracy : 23°C (73,4°F) ……… ±3%RH (40…60%rh)
23°C (73,4°F) ……….. ±5%RH (otherwise)
Working Range : 15…90%rh
Output : 0…10V or 4…20mA
Temperature:
Measuring Range : 0…50°C (32…122°F)²
Accuracy : (10…40°C ; 50…104°F)…….1 °C; ±1.8 °F
Output : 0…10V or 4…20mA


LK-LW-LP-LI SERIES GENERAL FEATURES
Humidity:
Accuracy : 30…80 %rh ….. 10…40°C ….. ±3 %rh
< 30 %rh or > 80 %rh ….. 10…40°C ….. ±5 %rh
Output Range : 0…100 %rh
Temperature:
Accuracy : 10…40°C ….. ±0.8 K
<10°C and >40°C ….. s. diagramm
Output Ranges : 0…+50°C
20…+80°C
– 30…+70°C
0…+100°C


LK and LW SERIES GENERAL FEATURES
Humidity:
Accuracy : 30…80 %rh ….. 10…40°C ….. ±3 %rh
< 30 %rh or > 80 %rh ….. 10…40°C ….. ±5 %rh
Output Range : 0…100 %rh
Temperature:
Accuracy : 10…40°C ….. ±0.8 K
<10°C and > 40°C ….. see diagramm
Output Ranges : -40 ….. +85°C


MCK … 4S0 and MCK … 1KD SERIES GENERAL FEATURES
Humidity:
Measuring Range : 0…100%rh
Accuracy : ±2.5%rh (10…40 °C, 10…90 %rh) ±1 digit
other range ……….. ±5% rh ±1 digit
Temperature:
Measuring Ranges : colour code
Accuracy : ± 0.5 K @ 23 °C ±1 digit