ECAP MODELS

ECAP capacitive level transmitter provides high precision proportional measurement opportunity in the level management of solid and liquid materials despite dust, foam, dirt or similar particles.

The capacitive measuring principle is based on detecting the changing capacity value depending on the mass between the electrode and the tank surface. The sensor electrode is immersed in the material up to the desired point after the installation. The first point where the sensor touches the fluid is defined as 4mA and the maximum point as 20mA (Optionally, the signal can be selected as 0-10V or 020mA). Thus, the sensor, which detects only the unique capacity created by the material, is not affected from other materials in the fluid and offers a high sensitivity.

ECAP capacitive transmitter is designed for the most difficult conditions. It offers a long lifetime even in high temperature and pressure environments.

Scope of application:

ECAP capacitive sensors do not have an area limit for industrial level measurement. It can be used in pump or valve control of water and fuel tanks, alarm output of aggressive chemicals, filling-discharge systems of dry solids such as dust or cereals, and even level detection of very hot and sticky materials such as bitumen. It is frequently preferred in fuel tracking and leakage systems, pharmaceutical industry, marine industry, plastic and similar raw material manufacturing, flour and feed storage.

ECAP101
For Conductive Liquids and Conductive Tanks

Complete Insulated Probe – Conductive Tank
1/2” BSP Male Thread , (Max. 4m.)
(-)1 …(+)100bar, (-)40…(+)150°C
4-20mA Two Wires (Std.)
Opt. 0/4-20mA – 0-10V Three Wires
Plastic Housing
a

ECAP102
For Conductive Liquids and Insulating Tanks

Complete Insulated Coaxial Probe – Nonconductive Tank
2” BSP Male Thread , (Max. 4m.)
(-)1…(+)100 bar , (-)40…(+)150°C
4-20mA Two Wires (Std.)
Opt. 0/4-20mA – 0-10V Three Wires
Plastic Housing

ECAP103 – Slim Type
For Conductive Liquids and Insulating Tanks

Complete Insulated Coaxial Probe – Nonconductive Tank
3/4” BSP Male Thread , (Max. 1m.)
(-)1…(+)60 bar , (-)40…(+)150°C
4-20mA Two Wires (Std.)
Opt. 0/4-20mA – 0-10V Three Wires
Plastic Housing

ECAP107 Rope Type
For Conductive Liquids and Conductive Tanks

Complete Insulated Rope – Conductive Tank
1 1/2” BSP Male Thread , (Max. 16m.)
2” BSP Male Thread , (Max. 32m.)
(-)1…(+)60bar , (-)40…(+)150°C
4-20mA Two Wires (Std.)
Opt. 0/4-20mA – 0-10V Three Wires
Plastic Housing

ECAP202
For Insulating Liquids

Noninsulated Coaxial Probe – Conductive – Nonconductive Tank
2” BSP Male Thread , (Max. 4m.)
(-)1…(+)100bar, (-)40…(+)150°C
4-20mA Two Wires (Std.)
Opt. 0/4-20mA – 0-10V Three Wires
Plastic Housing

ECAP203 – Slim Type
For Insulating Liquids

Noninsulated Coaxial Probe – Conductive – Nonconductive Tank
3/4” BSP Male Thread , (Max. 1m.)
(-)1…(+)100bar, (-)40…(+)150°C
4-20mA Two Wires (Std.)
Opt. 0/4-20mA – 0-10V Three Wires
Plastic Housing

ECAP204 – Rope Type
For Insulating Liquids and Conductive Tanks

Noninsulated Rope – Conductive Tank
1 1/2” BSP Male Thread , (Max.16m.)
2” BSP Male Thread , (Max. 32m.)
(-)1…(+)60bar, (-)40…(+)150°C
4-20mA Two Wires (Std.)
Opt. 0/4-20mA – 0-10V Three Wires
Plastic Housing

ECAP205
For Insulating Liquids and Conductive Tanks

Noninsulated Probe – Conductive Tank
1” BSP Male Thread , (Max. 6m.)
(-)1…(+)60bar , (-)40…(+)150°C
4-20mA Two Wire (Std.)
Opt. 0/4-20mA – 0-10V Three Wire
Plastic Housing

ECAP20s
For Insulating and Very High Temperature Liquids

1 1/2” BSP Male Thread , (Max. 4m.)
(-)1…(+)25bar, (-)40…(+)400°C
4-20mA Two Wires (std.)
Opt. 0/4-20mA – 0-10V Three Wires
Aluminum Housing

ECAP408
For Aggressive Chemicals

Double Noninsulated Probe – Conductive / Nonconductive Tank
2”BSP Male Thread , (Max. 6m.)
(-)1…(+)25 bar , (-)60…(+)150°C
4-20mA Two Wires (Std.)
Opt.0/4-20mA, 0-10V Three Wires
Plastic Housing
a